Protocol
- BACnet®
- MS/TP (EIA-485)
- Reliable Controls®
- Network (EIA-485/Token Bus)
4 Control-BASIC Programs
- User programmable control strategy
in a readable, BASIC-like language
- 2000 bytes per program
4 Inputs
- Universal ranges
- Jumper selectable 0-5 VDC,
4-20 mA, thermistor, and dry contact
4 Outputs
- Universal ranges
(base model)
- Scalable 0-12 VDC, 75 mA (max.)
- Single stage triac
- Dual stage triac
48 Variables
- Selectable standard and custom ranges,
as well as fixed or program-driven
values
|
|
4 PID Controllers
- Standard P, PI, or PID controllers
for closed loop control
2 Trend Logs
- Each trend log stores 72 samples of
6 points at programmable time intervals
4 Runtime Logs
- Totals the on time and records
the on/off times of a digital point
- Holds 48 samples
2 System Groups
- Related points can be
grouped in one display
- 50 points per group
1 Weekly Schedules
- 4 on/off times for each weekday and
2 override days
|
|
5 Custom Tables
- For creating custom input ranges
and Control-BASIC lookup tables
SMART-Net Port
- Networks up to 4 SMART-Sensors
32 Network In Points
32 Network Out Points
Warranty
- Industry Recognized 5 Year
Certification
|
|