Protocol
- BACnet®
- B/IP x 2, Ethernet, MS/TP and PTP
- Reliable Controls Protocol
- Backward compatibility with
previous generation systems
- Modbus
- Supports both RTU and TCP in both master and slave configurations
- SMTP
- Provides standard email communications
for broadcasting email alarms
- SMS
- SNMP
- Simple Network Management Protocol
Inputs and Outputs
- Up to 8 MACH-ProPoint expansion modules
- Maximum possible inputs of 128
- Maximum possible outputs of 64
- Maximum total I/O of 160 per controller
256 Variables
- Selectable standard and custom ranges,
as well as fixed program-driven values
|
|
64 PID Loops
- Standard P, PI, or PID controllers
for closed loop control
- BACnet loops supported
32 Weekly Schedules
- 4 On/Off times for each weekday and 2 override days
- BACnet schedules supported
8 Annual Schedules
- Days of the year designated as holidays
- BACnet schedules supported
20 Custom Tables
- For creating custom scaling functions
64 System Groups
- Allows related points to be
grouped on one display
- 160 points/group
128 Control-BASIC Programs
- User programmable control strategy
in a readable, BASIC-like language
- 3200 bytes per program
|
|
96 Trend Logs
- Each Trend Log stores 512 samples and up to
6 points
- Values recorded at user defined
intervals
- BACnet Trend Logs supported
128 Runtime Logs
- Totals the On time and records the On/Off times of a digital point
- Holds 200 events
128 User Passwords
- Protects access to system
- Each user is assigned a user name
and an access level
16 Custom Units
- 8 analog engineering units
- 8 digital engineering units
SMART-Net Port
- Networks up to 16 SMART-Sensors
Real-Time Clock
Warranty
Certification
|
|