Protocol
- BACnet®
- MS/TP (EIA-485)
- PTP (EIA-232)
- Reliable Controls®
- Network (EIA-485/Token Bus)
- PC & Modem (EIA-232)
8 Control-BASIC Programs
- User programmable control strategy
in a readable, BASIC-like language
- 2500 bytes per program
8 Inputs
- Universal ranges
- DIP switch selectable 0-5 VDC,
4-20 mA, thermistor/dry contact
8 Outputs
- Universal ranges
- Expanable to 32 outputs using
MACH2 expansion cards
- Optional switch control
(Hand/Off/Auto)
- HOA position feedback to
RC-Studio®
128 Variables
- Selectable standard and custom ranges,
as well as fixed or program-driven
values
|
|
32 PID Loops
- Standard P, PI, or PID controllers
for closed loop control
32 Trend Logs
- Each trend log stores 255 samples of
6 points at programmable time intervals
64 Runtime Logs
- Totals the on time and records
the on/off times of a digital point
- Holds 200 samples
32 System Groups
- Allows related points to be
grouped on one display
- 160 points per group
16 Weekly Schedules
- 4 on/off times for each weekday and
2 override days
8 Annual Schedules
- Days of the year designated as holidays
16 Variable Arrays
- Up to 128 elements in a
one-dimensional array
|
|
128 User Passwords
- Protects access to system
- Each user is assigned a user name
and an access level
5 Custom Tables
- For creating custom input ranges
16 Custom Units
- 8 analog engineering units
- 8 digital engineering units
SMART-Net Port
- Networks up to 16 SMART-Sensors
127 Network In Points
127 Network Out Points
Real-Time Clock
Warranty
- Industry Recognized 5 Year
Certification
|
|